How I check whether a PV string will over-voltage the charge controller on a cold morning
A charge controller that runs happily in August can refuse to start, or worse, take damage, on a clear January morning. The reason is usually not a mystery load. It is string voltage. Cold solar cells produce a higher open-circuit voltage than the number on the datasheet, and that number was measured at 25 °C. I check this before the array is landed on the roof, not after the first frost.
What actually rises in the cold
The figure that matters is the module's open-circuit voltage, Voc, and its temperature coefficient, usually listed as a negative percentage or in mV per °C. As the cells get colder, Voc climbs. The current drops a little, but the voltage is the one that can cross a limit.
The controller, or the MPPT input on an all-in-one unit, has a hard maximum voltage. Above that, protection may trip, or the input can be damaged. The check is simple in principle: estimate the highest string Voc you will ever see, and keep it below that limit with a margin.
A worked example (numbers are examples only)
Suppose each module is rated Voc 49.6 V at 25 °C, with a coefficient of −0.27%/°C. You plan four modules in series. The coldest morning you design for is −10 °C, which is 35 °C below the rating temperature.
The fractional rise is 35 × 0.27% = 9.45%. Each module's cold Voc is about 49.6 × 1.0945 ≈ 54.3 V. The string is 4 × 54.3 ≈ 217 V.
If the controller's maximum input is 200 V, this string is already over. If the maximum is 250 V, you have some room, but I still like a margin of at least 5–10%, because datasheet coefficients are typical values, and a very clear, still morning can be colder than the air temperature you planned for. Cells can sit below ambient just before sunrise.
A short way to repeat the arithmetic, if you like to check it in Python:
voc_stc = 49.6 # V, example only
coeff = -0.0027 # per °C, example only
t_min = -10 # °C, example only
n_series = 4
voc_cold = voc_stc * (1 + coeff * (t_min - 25))
print(round(voc_cold * n_series, 1))
That prints 217.1, the same estimate as above. Change the inputs to the figures on your own datasheets.
How I use the result
If the cold string voltage is too close to the limit, I do not hope the mornings are milder. I change the wiring: fewer modules in each series string, and more strings in parallel, so the voltage comes down and the current goes up. Then I check that the controller's maximum input current still covers the parallel combination, and that the cable and fuse sizes still fit.
I also check the other end of the window. In hot weather the voltage falls. A string that is only just above the MPPT start voltage in a datasheet at 25 °C can drop out of the window on a hot roof. The cold-morning check and the hot-afternoon check are two halves of the same job.
Where I look the numbers up
The module Voc and coefficient come from the module datasheet, not from a sales sheet that only lists wattage. The limit comes from the controller or inverter manual, the "maximum PV open-circuit voltage" line, which is not the same as the MPPT operating range. If you want a longer walkthrough of string voltage and MPPT input limits, that page works through the same cold-weather arithmetic. Wiring diagrams and string examples are also collected at https://solarenergystoragesystem.com/en/design-library.
Do the sum on paper or in a script, and write the assumed temperature next to it. Keep that sheet with the as-built notes.
Disclosure: I work with TORCHN. Yangzhou Weikechuang handles export trade and projects, and Yangzhou Dongtai handles production; both share the TORCHN brand.